Earth Transition Resistance Value

Standards and many organizations state that the earth transition resistance should be less than 2 ohms. This resistance should be measured by disconnecting other conductors from the earthing system.

Current Carrying Capacity

It is a capacity related to lightning current and should not be neglected. In order to reduce the impedance, it is necessary to ground with three points parallel to each other instead of grounding with a long conductor in one direction.

Equipotential Bond

The standards state that lightning rod earthing should be combined with structure earthing. All conductors within the structure (chimney, shields, telecommunication or electrical cables) should be connected using equipotential bonding busbars with a minimum cross-section of 16 mm2 for copper and 50 mm2 for steel. Unshielded telecommunication or electrical cables should be connected to the down conductor with a ‘surge arrester’.